Custom Search

News World

Nov 16, 2008

Surge Arrestor > TITAN DR Surge Protective Devices (SPD)

Introduction

These Surge Protective Devices (SPD) provide surge protection for electrical and automation cabinets. They can be mounted on standard 35 mm rail near the incoming power source to isolate the cabinet from the outside environment. This product is ideal for manufacturers and electrical installers requiring designed-in power protection.
NOTE: Must be installed with the proper Merlin Gerin Supplementary Protector (MGSP).



DIN Rail mounted surge protection

EFI’s Titan DR SPD systems provide highquality surge protection for electrical and automation cabinets. The Titan DR can be mounted on standard 35 mm rail prior to the incoming power source to isolate the cabinet from the outside environment. This product is ideal for manufacturers and electrical installers requiring designedin power protection.



DANGER

Hazard Of Electric Shock, Explosion, Or Arc Flash

· This equipment must be installed and serviced only by qualified electrical personnel in accordance with National and Local Electrical Codes.

· Turn off all power supplying this equipment before working on or inside equipment.

· Always use a properly rated voltage sensing device to confirm power is off.

· Replace all devices, doors, and covers before turning on power to this equipment.

· Do not apply petroleum-based products to non-metallic parts.

Failure to follow these instructions will result in death or serious injury.



CAUTION

HAZARD OF Equipment Damage

· Megger® or hi-potential tests will damage this surge protective device. Turn off all power supplying the equipment and isolate the surge protective device before testing.

· Must be installed with the proper Merlin Gerin Supplementary Protector (MGSP).

· Not for use on ungrounded systems.

Failure to follow these instructions can result in equipment damage.



APPLICATIONS

EFI’s new Titan DR Surge Protection Devices (SPD) provide
protection for single and multi-pole applications. The DR is ideal for
manufacturers and integrators of industrial, medical and commercial
instrumentation equipment.



SUPERIOR PE RFORMANCE
The Titan DR provides protection up to 80kA from voltage surges generated by lightning, power supplier network switching, motors, frequency converters, etc.
The Titan DR provides safe and reliable operation by incorporating thermal fusing. Each MOV is individually fused for maximum safety.
The Titan DR has been tested in accordance with UL 1449-2, CE and IEC 61643-1.



EASY INSTALLATION
The Titan DR mounts quickly and easily to mounting rails (35mm).
25mm2 connectors provide easy parallel connection providing greater
installation flexibility, even where space is limited.
The plug-in module of the single pole device allows replacement of a
damaged SPD while still connected to the mounting rail and power.



PLUG – IN


Single pole devices feature plug-in module design. User-replaceable module allows easy replacement of damaged SPD modules without any electrical wiring. Plug-in module also provides high flexibility when testing the isolation resistance of electrical cabinets.

Contact
Mr. Leong
Leatrimatik Sdn. Bhd
No. 4,
Jalan Tpk 2/4,
Taman Perindustrian Kinrara,
Batu 7 1/2, Off Jalan Puchong, 47100 Puchong, Selangor D.E. Malaysia
aldemar.guerra@us.schneider-electric.com

or

Aldemar Guerra
Technical Sales Manager
Efi Electronics Europe S.L.
C/ Albert Einstein 43
08940, Cornella de Llobregat (Spain)
Tel. : +34 93 4800630
Fax : +34 93 3777859
Mobile : +34 618815776
http://www.efinet.com
E-mail: aguerra@efinet.com

No comments:

IT Conversations

Moneycontrol Latest News

Latest new pages on Computer Hope

Latest from Infoworld

Door Lock